60Hz Googol Natural Gas Engine for Generator 160kw-1028kw

60Hz Googol Natural Gas Engine for Generator 160kW-1028kW Note: 1. All engine parameters are in accordance with ISO3046, ISO8528. 2. All engine parameters are based on 25°C / 100kPa environment conditions. 3. Application for Power Generation, Marine, Pump Driving, CHP power plant. Applied Gas: Natural Gas, Biogas, City Sewage Gas, Landfill Gas, Oil Gas, Farm Biogas, Coal Mine Gas, etc. Acceptable Fuel Gas Pressure: 5~12kPa CH4 Content: For Natural Gas ≥ 85% CH4, for Biogas ≥ 40% Gas Heat Value ≥ 5500kcal/Nm³ (23MJ/Nm³). Genset output power increases as gas heat value increases. If using low heat value gas (<5500kcal/Nm³), it will lower the power efficiency. Gas should not contain free water or materials; impurities size should be less than 5μm. H2S Content ≤ 200mg/Nm³ NH3 Content ≤ 20mg/Nm³ Impurities Content ≤ 30mg/Nm³; Size ≤ 5μm Water Content ≤ 40g/Nm³, no free water. Acceptable Working Conditions: Ambient Temperature: -10°C ~ +40°C (Preheater or antifreeze needed for below 0°C) Relative Humidity: <90% (20°C) Altitude: ≤ 1000m Normal Working Conditions: Genset can run at rated power under the following conditions: Atmospheric Pressure: 100kPa, Ambient Temp: 20°C, Relative Humidity: 30%. Standard Scope of Supply: 1. Gas Engine 2. AC Generator 3. Common Frame 4. Control Panel 5. Ignition System: Ignition Controller, Ignition Coils, Output Harness, Pickup Magnetic, Trigger Disc, PolyMot High Tension Lead, Spark Plug 6. Detonation Controller System: DetCon20 control unit, Detonation Sensor, Cable & Knock Sensor 7. Electronic Speed Controller System: Integrated Throttle Body, Vari-Step Stepper Motor Card, Harness VariFuel, Electronic Speed Controller - ECON-4, Pickup Magnetic 8. Gas Mixer System: VariFuel Air/Fuel Ratio Mixer, VF Flange, VariStep Stepper Motor Card, Harness VariFuel, VariFuel2 Flow Body 9. Emission Control System: EmCon5 Control Unit, EmCon5 Sensor Harness, Knock Sensor 10. Valve: Gas Pressure Valve, Solenoid Valve, Cut-off Valve 11. Exhaust Bellows & Muffler 12. Radiator (optional) Warranty: All equipment is guaranteed for a period of 1000 hours running or 18 months from the date when the generator set has been delivered from the factory.
Genset Model HGGM200/6 HGGM250/6 HGGM325/6 HGGM400/6 HGGM500/6 HGGM650/6 HGGM1000/6 HGGM1285/6
Engine Model RTA780G2 RTA780G4 RTA890G2 RTA1120G2 RTA1340G2 JTA2160SG2 JTA3240SG2 JTA4320SG2
Rating Speed rpm 1800 1800 1800 1800 1800 1200 1200 1200
Frequency Hz 60 60 60 60 60 60 60 60
Generator Output (COP) kW 160 200 260 320 400 520 800 1028
Power Factor 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8
Gas Engine Parameter
Engine Output (COP) kW 180 222 278 355 438 629 842 1152
Air Ratio λ 1.67 1.7 1.7 1.7 1.7 1.7 1.7 1.7
Configuration 6 In Line 6 In Line 8 Vee 10 Vee 12 Vee 8 Vee 12 Vee 16 Vee
Displacement l 12.8 12.8 14.6 18.3 21.9 35.4 53.1 70.8
Bore mm 128 128 128 128 128 170 170 170
Stroke mm 166 166 142 142 142 195 195 195
Compression Ratio 11:1 11:1 12:1 12:1 12:1 12:1 12:1 12:1
Piston Speed m/s 9.96 9.96 8.52 8.52 8.52 7.8 7.8 7.8
Number of Flywheel Teeth 160 160 160 160 160 218 218 218
Flywheel House Size SAE1-14 SAE1-14 SAE1-14 SAE1-14 SAE1-14 SAE00-18 SAE00-21 SAE00-21
System Parameter
Oil Capacity l 40 40 70 80 90 160 180 240
Max. Allowed Oil Temperature °C 110 110 110 110 110 110 110 110
Oil Pressure Warning kPa 200 200 200 200 200 300 300 300
Oil Pressure Shutdown kPa 160 160 160 160 160 200 200 200
Coolant Capacity for Engine l 18 18 36 42 44 70 100 140
Max. Coolant Warning Temperature °C 90 90 90 90 90 93 93 93
Max. Coolant Shutdown Temperature °C 95 95 95 95 95 97 97 97
Max. Intercooler Outlet Temperature °C 50 50 50 50 50 40.5 40.5 40.5
Flow of Coolant Pump (JW) m³/h 24 24 30 30 30 39 39 64
Flow of Coolant Pump (LT) m³/h 14 14 14 14 14 36 36 60
Max. Exhaust Temperature °C 535 535 535 535 535 450 450 450
Exhaust Flow kg/h 697 871 1150 1383 1708 2971 4370 6044
Exhaust Flange Diameter mm 1*125 1*125 2*125 2*125 2*125 1*250 1*250 1*250
Charging Alternator Capacity A 35 35 35 35 35 55 55 55
Starting Voltage V 24 24 24 24 24 24 24 24
Thermal Balance
JW Coolant Heat ± 8% kW 102 129 158 185 226 310 420 542
CAC Intercooler Heat ± 8% kW 42 67 93
Exhaust Heat up to 120°C ± 8% kW 120 146 171 215 272 338 440 556
Energy Input kW 468 578 712 867 1078 1450 1951 2495
Electrical Efficiency % 34.2 34.6 36.5 36.9 37.1 39.5 41.0 41.2
Mechanical Efficiency % 36.6 36.7 38.5 38.8 39.2 41.7 43.0 43.2
Thermal Efficiency % 47.4 47.6 46.2 46.1 46.2 44.7 44.1 44.0
Total Efficiency % 81.6 82.2 82.7 83.0 83.3 84.2 85.1 85.2
Gas Consumption MJ/kWh 10.53 10.40 9.86 9.76 9.70 9.11 8.78 8.74
Generator Parameter
Generator Model ECO38-1SN/4 ECO38-3SN/4 ECO38-2LN/4 ECO40-1S/4 ECO40-2S/4 MX-500-6 MX-800-6 MX-1000-6
Generator Prime Output kW 176 216 288 384 432 550 880 1100
Generator Efficiency @ 0.8PF 93.4% 94.2% 94.8% 95.1% 94.7% 94.8% 95.3% 95.4%
Genset Dimension
Length mm 3100 3100 3300 3500 3600 4600 4500 5000
Width mm 1300 1300 1500 1500 1500 2190 1600 1600
Height mm 1700 1700 2000 2000 2000 2300 2200 2300
Genset Weight kg 2500 2500 3500 3900 4300 8250 10500 13500


60Hz Googol Natural Gas Engine for Generator 160kw-1028kw

Air Conditioning

Introduction to GENT air conditioning series products

GENT has a series of air conditioning unit that can directly blow air into the room to achieve indoor space cooling or heating. This series includes Evaporative Air Conditioning, Air To Air Heat Pump, Fan Coil and Water To Air Heat Pump. Each of these products is different and can meet the different needs of different users.

Among them, evaporative air conditioning is a single cooling central ac unit suitable for large indoor space cooling. This air conditioner adopts a spilt structure of indoor and outdoor units, with tap water as the cooling source, and achieves indoor space cooling by blowing air directly into the room.

The air to air heat pump is an central air conditioning unit designed by GENT specifically for greenhouse scenes. The unit uses air as the heating and cooling sources and blows air directly into the room to achieve indoor space heating and cooling.

Fan coil is a kind of indoor terminal suitable for heat pump that produce water. Fan coil can achieve the heat exchange between the water produced by the heat pump and indoor air by blowing air into the room, thereby achieving indoor space heating and cooling.

Water to air heat pump is a heating and air conditioning water source hvac unit that outputs air directly. Different from ordinary Water Source Heat Pump, this unit does can blowing air directly into the room to achieve indoor space heating and cooling without indoor terminals.

Users who have indoor space heating and cooling needs can choose the corresponding unit according to the specific characteristics of each product. There is always a unit that can meet your needs. We look forward to receiving your consultation information.

Air Conditioning Unit,Heating And Air Conditioning,Hvac Unit,Central Ac Unit,Central Air Conditioning Unit

GUANGZHOU GENT NEW ENERGY TECHNOLOGY CO., LTD , https://www.gentgz.com